Products
 

Features:

1 Modular design with N+X redundancy and hot plugging ,easy to expand the capacity

2 High power density with footprints of less than 0.66 ㎡ up to 900KVA in parallel

3 Full DSP control of high stability, reliability and safety.

4 Integrated IGBT module with improved performance and reduced size,

5 Excellent input performances for complete compatibility with input PF of 99% and wide range of voltage ±20%(Normally working) and -20%-40%(Derate linearly)

6 Easy load mode for test ,saving more than 90% power consumption

7 Intelligent sleep mode for energy saving and prolong the service life of the system

8 Smart ging management system,Intelligently control the whole process of the ging,effectively improve the life span of the battery.

9 Batterycold start, the system can start up without main input

10 Friendly user interface with color touch screen of 10.4 inches

11 Interface:RS232, RS485, USB, Dry contact;Parallel, SNMP, Expansion Dry Contact card, Remote Monitor, LBS(Optional)


Specifications:

Power Rating

Capacity (kVA)

30~300

Capacity (kW)

27~270

Main Input

Grid System

3 Phases + Neutral + Ground

Rated Input Voltage

380/400/415VAC (Line-Line)

Rated Frequency

50/60Hz

Input Voltage Range

304~478Vac (Line-Line),full load

228V~304Vac (Line-Line),load decrease linearly                                           
according to the min phase voltage

Input Frequency Range

40Hz70Hz

Input Power Factor


>0.99

Input Current THDi

<3% (full Linear Load)

Bypass Input

Rated Bypass Voltage

380/400/415VAC (Line-Line)

Rated Frequency

50/60Hz

Bypass Voltage Range

Selectable,  default -20%+15%
Up limited: +10%, +15%, +20%, +25%
Down limited: -10%,  -15%, -20%, -30%,  -40%

Bypass Frequency Range

Selectable, ±1Hz, ±3Hz, ±5Hz

Bypass Overload

110% Long term operation
110%~125% for 5min
125%~150% for 1min
150%~400% for 1s
>400% ,less than 200ms

Output

Rated Inverter Voltage

380/400/415VAC (Line-Line)

Rated Frequency

50/60Hz

Output Power Factor

0.9

Voltage precision

±1.5%(0-100% linear load)

Transient Response

<5% for step load  (20% - 80% -20%)

Transient recovery

< 30ms for step load (0% - 100% -0%)

Output Voltage THDu

<1% from 0% to 100% linear load
<6% full non-linear load according to IEC/EN62040-3

Inverter Overload


110%, 60min;
125%,10min;
150%,1min;
>150%,200ms

Frequency Regulation

50/60Hz±0.1%

Synonized Range

Settable, ±0.5Hz  ±5Hz, default ±3Hz

Synonized Slew Rate

Settable, 0.5Hz/S  3Hz/S, default 0.5Hz/S

Battery And Charger

Battery Rate Voltage

±240VDC

Charger Voltage precision

1%

Charger Power

max=20%

Efficiency

Normal Operation

>95%

Battery Operation

>95%

ECO Operation

>99%

System

Display

LED + LCD + Touch screen

Interface

Standard:RS232, RS485, USB,Dry Contact
Option: SNMP,AS/400

Environmental

Operation Temperature

 40 

Storage Temperature

-40  70 

Relative Humidity

 95% Non condencing

Noise (1 meter)

65dB @ 100% load, 62dB @ 45% load

Altitude

<1000m, Load derated 1% per100mFrom 1000  2000m

Phisical data

Module Dimension(W*D*H,mm)

460*790*134

Module Weight (kg)

34

Cabinet Dimension (W*D*H,mm)

600*1100*2000

Cabinet Weigh (kg)

220

Home About Us Products Support Solution News Honor Contact Us